Wiki source code of ABB - PVS 800-57B
Last modified by Wim Verheirstraeten on 2023/10/06 18:36
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | **Communication 1** | ||
2 | |||
3 | |(% style="width:402px" %)Communication interface|(% style="width:546px" %)RS485 | ||
4 | |(% style="width:402px" %)Max. number of devices per bus|(% style="width:546px" %)22 | ||
5 | |(% style="width:402px" %)Protocol|(% style="width:546px" %)ModbusRTU | ||
6 | |(% style="width:402px" %)Bus speed|(% style="width:546px" %)9600 bps, 19200 bps, 38400 bps, 57600 bps, 115200 bps | ||
7 | |(% style="width:402px" %)Bus speed default|(% style="width:546px" %)9600 bps | ||
8 | |(% style="width:402px" %)Default address|(% style="width:546px" %)1 | ||
9 | |(% style="width:402px" %)Alarm monitoring|(% style="width:546px" %)Yes | ||
10 | |||
11 | **Communication 2** | ||
12 | |||
13 | |(% style="width:402px" %)Communication interface|(% style="width:547px" %)Ethernet | ||
14 | |(% style="width:402px" %)Max. number of devices|(% style="width:547px" %)100 | ||
15 | |(% style="width:402px" %)Protocol|(% style="width:547px" %)ModbusTCP | ||
16 | |(% style="width:402px" %)Port|(% style="width:547px" %)502 | ||
17 | |(% style="width:402px" %)Default address|(% style="width:547px" %)1 | ||
18 | |(% style="width:402px" %)Remote Device Access|(% style="width:547px" %)No | ||
19 | |(% style="width:402px" %)Alarm monitoring|(% style="width:547px" %)Yes | ||
20 | |||
21 | **Measurement values recorded** | ||
22 | |||
23 | |(% style="width:404px" %)COS_PHI|(% style="width:545px" %)Power factor (cos phi) | ||
24 | |(% style="width:404px" %)ERROR (1,...x)|(% style="width:545px" %)Error (1,...x) | ||
25 | |(% style="width:404px" %)E_DAY|(% style="width:545px" %)Energy generated per day | ||
26 | |(% style="width:404px" %)E_TOTAL|(% style="width:545px" %)Energy total | ||
27 | |(% style="width:404px" %)F_AC|(% style="width:545px" %)Grid frequency | ||
28 | |(% style="width:404px" %)I_AC|(% style="width:545px" %)Current AC | ||
29 | |(% style="width:404px" %)I_DC|(% style="width:545px" %)Current DC total | ||
30 | |(% style="width:404px" %)I_DCX_Y|(% style="width:545px" %)Current DC (1,...x).(1,...x) | ||
31 | |(% style="width:404px" %)P_AC|(% style="width:545px" %)Power AC | ||
32 | |(% style="width:404px" %)Q_AC|(% style="width:545px" %)Reactive power | ||
33 | |(% style="width:404px" %)R_ISO|(% style="width:545px" %)Insulation resistance | ||
34 | |(% style="width:404px" %)S_AC|(% style="width:545px" %)Apparent power | ||
35 | |(% style="width:404px" %)T (1,...x)|(% style="width:545px" %)Temperature (1,...x) | ||
36 | |(% style="width:404px" %)U_AC|(% style="width:545px" %)Voltage AC | ||
37 | |(% style="width:404px" %)U_AC1|(% style="width:545px" %)Voltage AC phase 1 | ||
38 | |(% style="width:404px" %)U_AC2|(% style="width:545px" %)Voltage AC phase 2 | ||
39 | |(% style="width:404px" %)U_AC3|(% style="width:545px" %)Voltage AC phase 3 | ||
40 | |(% style="width:404px" %)U_AC_L1L2|(% style="width:545px" %)Phase voltage L1L2 | ||
41 | |(% style="width:404px" %)U_AC_L2L3|(% style="width:545px" %)Phase voltage L2L3 | ||
42 | |(% style="width:404px" %)U_AC_L3L1|(% style="width:545px" %)Phase voltage L3L1 | ||
43 | |(% style="width:404px" %)U_DC|(% style="width:545px" %)Voltage DC | ||
44 | |||
45 | **Supported Devices** | ||
46 | |||
47 | PVS 800-57B |